Hard drives... how hot is too hot? At one host a drive is 50C!

Collapse
X
 
  • Time
  • Show
Clear All
new posts
  • rowan
    Too lazy to set a custom title
    • Mar 2002
    • 17393

    #1

    Hard drives... how hot is too hot? At one host a drive is 50C!

    I noticed recently that the HD temperature reported by SMART on one of my servers is looking kinda high. There are two identical drives in the server and over the past 24h the temp of each has ranged from 45-50C. A few months ago the drive temps were at 40C, which makes me wonder whether it's a data centre cooling issue.

    If I'm reading the SMART values right the "maximum" temp threshhold is set to trip above 55C, so it's not far off.

    At another host a similar set of drives (same brand and capacity) is currently 32C.

    Thoughts?
  • camgirlshide
    Confirmed User
    • Jan 2005
    • 1558

    #2
    50C is not that hot.
    Most equipment is tested to work at 50C ambient
    Useful adult webmaster links -
    Alphabetical list of solo models with webcam
    Stats on my best converting affiliate programs - camgirlshide webmaster blog
    complete list of affiliate programs I use.

    Comment

    • Spunky
      I need a beer
      • Jun 2002
      • 133978

      #3
      That's not abnormal

      Comment

      • rowan
        Too lazy to set a custom title
        • Mar 2002
        • 17393

        #4
        SMART 190
        Value: 050 (50C)
        Worst: 044 (56C)
        Threshold: 045 (55C)

        Damn, looks like it's already been overtemp. 56C!

        Comment

        • rowan
          Too lazy to set a custom title
          • Mar 2002
          • 17393

          #5
          If it's fine then why is the SMART "failure" threshold set to 55C?

          Comment

          • Spudstr
            Confirmed User
            • Jan 2003
            • 2321

            #6
            56C = 132F! Thats hot!
            Managed Hosting - Colocation - Network Services
            Yellow Fiber Networks
            icq: 19876563

            Comment

            • rowan
              Too lazy to set a custom title
              • Mar 2002
              • 17393

              #7
              bump5678

              Comment

              • cess
                Confirmed User
                • Sep 2006
                • 2921

                #8
                Originally posted by rowan
                If it's fine then why is the SMART "failure" threshold set to 55C?
                Because it's warning you before it gets too hot I would assume. Most HDD can handle around 150F/65C or so. But running them around that can wear down the life of the drive, I keep mine at 90F.

                Comment

                • uno
                  RIP Dodger. BEST.CAT.EVER
                  • Dec 2002
                  • 18450

                  #9
                  Originally posted by Spudstr
                  56C = 132F! Thats hot!
                  Thank you for stating that in non communist terms.
                  -uno
                  icq: 111-914
                  CrazyBabe.com - porn art
                  MojoHost - For all your hosting needs, present and future. Tell them I sent ya!

                  Comment

                  • Iron Fist
                    Too lazy to set a custom title
                    • Dec 2006
                    • 23400

                    #10
                    Originally posted by uno
                    Thank you for stating that in non communist terms.
                    i like waffles

                    Comment

                    • borys
                      Confirmed User
                      • Oct 2002
                      • 146

                      #11
                      Originally posted by rowan
                      A few months ago the drive temps were at 40C, which makes me wonder whether it's a data centre cooling issue.
                      Have your host check the box for broken fans.

                      Comment

                      • split_joel
                        Confirmed User
                        • Jan 2005
                        • 2270

                        #12
                        does not mean your host has heating issues could be a fan motor has died, have your service provider check out the server.
                        E-mail marketing - Automation Scripting - IP Space
                        AIM: splitjoelp ICQ: 254759453 skype - splitjoelp 702-941-6465

                        Comment

                        • rowan
                          Too lazy to set a custom title
                          • Mar 2002
                          • 17393

                          #13
                          It *is* a D/C cooling issue. Good because my server doesn't have to be taken offline to check fans, bad because in the long run this may have shortened the useful life of some of the components in it.....